Wire Size Guide: AWG Chart & NEC Ampacity Tables

Quick Answer: 14 AWG handles 15A (1,800W @ 120V). 12 AWG handles 20A (2,400W). 10 AWG handles 30A (7,200W @ 240V). Always check NEC Table 310.16 for ampacity at your insulation temperature rating.

American Wire Gauge (AWG) System

AWG is a standardized wire gauge system used in North America. The gauge number is inversely related to wire diameter — lower AWG = thicker wire = more ampacity. Going down 3 AWG numbers approximately doubles the cross-sectional area.

NEC Ampacity Table (Table 310.16)

AWGDiameter (in)Area (cmils)Cu 60°CCu 75°CCu 90°CAl 75°CTypical Use
140.06414,11015A20A25A15A branch circuits (lighting)
120.08086,53020A25A30A20A20A branch circuits (receptacles)
100.101910,38030A35A40A30A30A circuits (dryer, AC)
80.128516,51040A50A55A40A40-50A circuits (range, oven)
60.162026,25055A65A75A50A60A subpanel feeders
40.204341,74070A85A95A65A70-100A feeders
20.257666,36095A115A130A90A100A service entrance
1/00.3249105,600125A150A170A120A150A service entrance
2/00.3648133,100145A175A195A135A200A service entrance
4/00.4600211,600195A230A260A180A200A+ service entrance

Temperature ratings: 60°C = TW, UF insulation. 75°C = THW, THWN insulation. 90°C = THHN, XHHW insulation. Most residential uses 60°C column for safety margin.

Copper vs Aluminum Wire

PropertyCopperAluminum
Conductivity100% (baseline)61% of copper
Ampacity (same gauge)HigherLower (need 2 AWG sizes larger)
CostHigherLower (40–60% savings)
WeightHeavierLighter (50% of copper)
OxidationMinimalRequires anti-oxidant compound
NEC RequirementStandardMust be rated AL/CU for connections
Typical UseBranch circuits (15–50A)Service entrance, feeders (100A+)

Voltage Drop by Wire Size (per 100 ft round trip)

AWGResistance (Ω/1000ft)10A @ 120V15A @ 120V20A @ 120V30A @ 240V
142.5255.05V (4.2%)7.58V (6.3%)
121.5883.18V (2.6%)4.76V (4.0%)6.35V (5.3%)
100.9992.00V (1.7%)3.00V (2.5%)4.00V (3.3%)
80.6281.26V (1.0%)1.88V (1.6%)2.51V (2.1%)
60.3952.37V (1.0%)

NEC recommendation: Keep voltage drop under 3% for branch circuits, 5% total (feeder + branch).

Common Wire Sizing Mistakes

Standards Reference

Frequently Asked Questions

What wire size do I need for 20 amps?

Use 12 AWG copper wire for 20A circuits. NEC Table 310.16 rates 12 AWG at 25A (75°C insulation), but NEC 240.4(D) limits it to 20A maximum overcurrent protection. For long runs (>50 ft), consider upsizing to 10 AWG to stay under 3% voltage drop.

Can I use 14 AWG on a 20A breaker?

No. NEC 240.4(D) limits 14 AWG copper to 15A maximum overcurrent protection. Using 14 AWG on a 20A breaker is a code violation and fire hazard. The wire could overheat before the breaker trips.

What's the difference between copper and aluminum wire?

Copper has 61% higher conductivity than aluminum, so aluminum must be 2 AWG sizes larger for the same ampacity. Aluminum is cheaper and lighter, making it preferred for service entrance and large feeders (100A+). Always use AL/CU-rated connectors when terminating aluminum wire.

How do I calculate voltage drop?

V_drop = I × R × 2 × L / 1000, where I = current (amps), R = resistance per 1000 ft (from wire table), L = one-way length (ft). The factor of 2 accounts for the round trip. NEC recommends keeping voltage drop under 3% for branch circuits.

What does AWG stand for?

AWG stands for American Wire Gauge, the standard system for wire diameter in North America. The gauge numbers are inversely proportional to wire size: 10 AWG is thicker than 14 AWG. Going down 3 AWG numbers approximately doubles the cross-sectional area and ampacity.

Disclaimer: This guide is for educational and preliminary design purposes only. Always verify final equipment sizing against local codes and professional engineering requirements.