Voltage Drop Guide: NEC Limits, Formula & Charts

Quick Answer: NEC recommends <3% voltage drop for branch circuits and <5% total (feeder + branch). Formula: Vdrop = 2 × I × L × R / 1000. For a 20A, 100-ft run: 14 AWG = 10.1V (8.4%), 12 AWG = 6.4V (5.3%), 10 AWG = 4.0V (3.3%).

What Is Voltage Drop?

Voltage drop is the reduction in electrical pressure as current flows through wire resistance. Every conductor has resistance — the longer and thinner the wire, the more voltage is lost. Excessive voltage drop causes:

Voltage Drop Formula

Vdrop = (2 × I × L × R) / 1000

Percentage: Vdrop% = (Vdrop / Vsource) × 100

NEC Voltage Drop Recommendations

Circuit TypeMax Voltage DropNEC Reference
Branch circuit (feeder to panel)3%NEC 215.2(A)(1) FPN
Branch circuit (panel to device)3%NEC 210.19(A) FPN
Combined (feeder + branch)5%NEC FPN recommendation
Fire alarm circuits5%NEC 760.121

Note: These are FPN (Fine Print Notes) — recommendations, not enforceable code. However, they represent best practice and most jurisdictions enforce them.

Voltage Drop Chart (120V, copper wire)

Wire AWGResistance Ω/1000ft50 ft100 ft150 ft200 ftMax length @ 15A (3%)
142.5252.5%5.0%7.6%10.1%47 ft
121.5881.6%3.2%4.8%6.4%75 ft
100.9991.0%2.0%3.0%4.0%120 ft
80.6280.6%1.3%1.9%2.5%191 ft
60.3950.4%0.8%1.2%1.6%304 ft

Values at 15A, 120V. For 20A: multiply percentage by 1.33. For 240V: divide percentage by 2.

Worked Examples

Example 1: 120V, 15A, 100 ft

14 AWG: Vdrop = (2 × 15 × 100 × 2.525) / 1000 = 7.58V = 6.3% ❌ (exceeds 3%)

12 AWG: Vdrop = (2 × 15 × 100 × 1.588) / 1000 = 4.76V = 4.0%

10 AWG: Vdrop = (2 × 15 × 100 × 0.999) / 1000 = 3.00V = 2.5%

Result: Use 10 AWG for this 100-ft, 15A, 120V circuit.

Example 2: 240V, 30A, 150 ft (AC unit)

10 AWG: Vdrop = (2 × 30 × 150 × 0.999) / 1000 = 8.99V = 3.7%

8 AWG: Vdrop = (2 × 30 × 150 × 0.628) / 1000 = 5.65V = 2.4%

Result: Use 8 AWG for this 240V, 30A AC circuit at 150 ft.

Common Voltage Drop Mistakes

Standards Reference

Frequently Asked Questions

What is acceptable voltage drop?

NEC recommends less than 3% voltage drop for branch circuits and less than 5% total (feeder + branch combined). For a 120V circuit, 3% = 3.6V. For a 240V circuit, 3% = 7.2V. Fire alarm circuits have a 5% maximum.

How do I calculate voltage drop?

V_drop = (2 × I × L × R) / 1000, where I = current (amps), L = one-way wire length (ft), R = wire resistance per 1000 ft (from NEC Table 8 or wire manufacturer data). The factor of 2 accounts for the round-trip distance.

Does voltage drop affect 240V circuits?

Yes, but 240V circuits have half the percentage drop for the same absolute voltage loss. A 6V drop on 120V is 5%, but on 240V it's only 2.5%. This is one advantage of 240V for long runs and high-power loads.

When should I upsize wire for voltage drop?

When the calculated voltage drop exceeds 3% at the expected load current. Common scenarios: garage subpanels, outdoor outlets, shed wiring, landscape lighting, and any circuit with wire runs over 75 ft on 120V or 150 ft on 240V.

Does voltage drop waste electricity?

Yes. The voltage lost in the wire is dissipated as heat (P = I²R). A 15A circuit with 5% voltage drop wastes about 90W in the wire. Over a year, that's ~790 kWh or about $100. Proper wire sizing pays for itself in energy savings.

Disclaimer: This guide is for educational and preliminary design purposes only. Always verify final equipment sizing against local codes and professional engineering requirements.