← Back to All Calculators

Wire Size Calculator

Determine minimum wire gauge for current and voltage drop

Input Parameters

About This Calculator

  • Checks both ampacity and voltage drop
  • Recommends the larger of the two
  • NEC recommends ≤3% branch circuit

📖 Read the Complete Guide →

How this wire size calculator works

Two criteria determine wire size: ampacity (must carry the current) and voltage drop (must not exceed limit over length).

The calculator picks the larger wire. A = I × 2 × ρ × L / (V × drop%) for single-phase.

FAQ

How to calculate wire size?

Check ampacity and voltage drop, use larger wire.

Wire for 30 amps?

#10 AWG copper minimum. Check V-drop for long runs.

Copper vs aluminum?

Aluminum needs 2 sizes larger for same ampacity.

Common Wire Sizing Mistakes — What Electricians & Engineers Get Wrong

Using 90°C ampacity but forgetting 75°C terminal limit

NEC Table 310.16 shows three columns: 60°C, 75°C, and 90°C. THHN wire is rated 90°C, so engineers sometimes use the 90°C column — but NEC 110.14(C) requires using the lower of conductor and terminal rating. Most breakers and equipment terminals are rated 75°C (or 60°C on older panels). Using the 90°C column on a 75°C terminal can result in a conductor that is technically legal by ampacity but illegal at the connection point.

Forgetting conduit fill derating

NEC Table 310.15(C)(1) requires ampacity correction when more than 3 current-carrying conductors share a conduit. Four conductors: derate to 80%. Seven conductors: derate to 70%. A common mistake is to size each wire independently and then bundle them — the bundled assembly may need the next larger AWG to compensate. The derating applies to current-carrying conductors only; a ground wire does not count.

Voltage drop on one-way distance vs. round-trip

Voltage drop occurs across both the hot conductor and the neutral/return conductor. For single-phase circuits, use 2 × one-way length in the formula. A 100 ft circuit has 200 ft of total conductor path. This is the single most common calculation error — using one-way distance produces a wire that drops twice the intended voltage and is undersized for the run.

AWG to mm² substitution without checking standard sizes

12 AWG has an actual cross-section of 3.31 mm², but the nearest IEC standard size is 4 mm². Substituting the exact mm² equivalent (3.31 mm²) is non-standard — IEC 60228 defines discrete cable sizes (1.5, 2.5, 4, 6, 10, 16 mm²…). Always round up to the next standard IEC size. Using 3.31 mm² on a datasheet will confuse suppliers outside North America who can only source standard sizes.

Related Calculators