Voltage Drop Formula: How to Calculate Step by Step

Voltage Drop Formulas

Single-Phase (120V or 240V)

VD = 2 × L × I × R ÷ 1000

The factor of 2 accounts for the round-trip (hot + neutral).

Three-Phase

VD = √3 × L × I × R ÷ 1000

√3 ≈ 1.732. The three-phase formula uses √3 instead of 2 because the return path is shared across phases.

Worked Example

Scenario: 120V circuit, 20A load, 100 ft run, 12 AWG copper wire.

Step 1: Find resistance from NEC Table 8: 12 AWG copper = 2.01 ohms/1000ft (DC resistance at 75°C)

Step 2: VD = 2 × 100 × 20 × 2.01 ÷ 1000 = 8.04V

Step 3: %VD = 8.04 ÷ 120 × 100 = 6.7%

Result: 6.7% exceeds the NEC 3% recommendation. Use 10 AWG (1.24 ohms/1000ft): VD = 2 × 100 × 20 × 1.24 ÷ 1000 = 4.96V = 4.1%. Still above 3%? Try 8 AWG: VD = 3.12V = 2.6% ✓

NEC Voltage Drop Recommendations

Circuit TypeMax Voltage Drop120V Circuit240V Circuit
Branch circuit (NEC recommendation)3%3.6V7.2V
Feeder + branch combined5%6.0V12.0V
Fire alarm circuits (NFPA 72)10%12.0V24.0V

Note: NEC 210.19 and 215.2 use "shall" for ampacity but "should" for voltage drop — it's a recommendation, not a code violation. However, exceeding 3% causes equipment problems and energy waste.

Frequently Asked Questions

What is the voltage drop formula?

Single-phase: VD = 2 × L × I × R ÷ 1000. Three-phase: VD = √3 × L × I × R ÷ 1000. Where L = length (ft), I = current (amps), R = resistance (ohms/1000ft) from NEC Chapter 9 Table 8.

What is the allowable voltage drop?

NEC recommends (not requires) max 3% voltage drop on branch circuits and 5% total (feeder + branch). For a 120V circuit: 3% = 3.6V drop, 5% = 6V drop. For 240V: 3% = 7.2V, 5% = 12V.

How do I reduce voltage drop?

Use larger wire (lower gauge), shorter circuit runs, or higher voltage (240V instead of 120V). For a given load: doubling the wire size halves the voltage drop. Moving from 120V to 240V halves the current, which halves the drop.

Disclaimer: For preliminary design only. Verify against local codes and professional engineering requirements.