Voltage Drop Formula: How to Calculate Step by Step

Voltage Drop Formulas

Single-Phase (120V or 240V)

VD = 2 × L × I × R ÷ 1000

The factor of 2 accounts for the round-trip (hot + neutral).

Three-Phase

VD = √3 × L × I × R ÷ 1000

√3 ≈ 1.732. The three-phase formula uses √3 instead of 2 because the return path is shared across phases.

Worked Example

Scenario: 120V circuit, 20A load, 100 ft run, 12 AWG copper wire.

Step 1: Find resistance from NEC Table 8: 12 AWG copper = 2.01 ohms/1000ft (DC resistance at 75°C)

Step 2: VD = 2 × 100 × 20 × 2.01 ÷ 1000 = 8.04V

Step 3: %VD = 8.04 ÷ 120 × 100 = 6.7%

Result: 6.7% exceeds the NEC 3% recommendation. Use 10 AWG (1.24 ohms/1000ft): VD = 2 × 100 × 20 × 1.24 ÷ 1000 = 4.96V = 4.1%. Still above 3%? Try 8 AWG: VD = 3.12V = 2.6% ✓

NEC Voltage Drop Recommendations

Circuit TypeMax Voltage Drop120V Circuit240V Circuit
Branch circuit (NEC recommendation)3%3.6V7.2V
Feeder + branch combined5%6.0V12.0V
Fire alarm circuits (NFPA 72)10%12.0V24.0V

Note: NEC 210.19 and 215.2 use "shall" for ampacity but "should" for voltage drop — it's a recommendation, not a code violation. However, exceeding 3% causes equipment problems and energy waste.

Frequently Asked Questions

What is the voltage drop formula?

Single-phase: VD = 2 × L × I × R ÷ 1000. Three-phase: VD = √3 × L × I × R ÷ 1000. Where L = length (ft), I = current (amps), R = resistance (ohms/1000ft) from NEC Chapter 9 Table 8.

What is the allowable voltage drop?

NEC recommends (not requires) max 3% voltage drop on branch circuits and 5% total (feeder + branch). For a 120V circuit: 3% = 3.6V drop, 5% = 6V drop. For 240V: 3% = 7.2V, 5% = 12V.

How do I reduce voltage drop?

Use larger wire (lower gauge), shorter circuit runs, or higher voltage (240V instead of 120V). For a given load: doubling the wire size halves the voltage drop. Moving from 120V to 240V halves the current, which halves the drop.

What NEC reference covers the voltage drop formula?

The NEC voltage drop recommendation is in Article 210.19(A)(1) Informational Note No. 1 for branch circuits and 215.2(A)(1) for feeders: keep combined voltage drop within 3% for supply conductors and 5% total from panel to the furthest load. These are fine-print recommendations, not mandatory limits.

Disclaimer: For preliminary design only. Verify against local codes and professional engineering requirements.