Power Guide: Watts, VA, Power Factor & Circuit Sizing

Quick Answer: Real power: P = V × I × PF (watts). Apparent power: S = V × I (VA). Power factor: PF = P / S. For a 120V motor drawing 10A at 0.8 PF: P = 120 × 10 × 0.8 = 960W, S = 1,200VA. Circuit must be sized for amps (I), not watts.

Types of Electrical Power

Power triangle: S² = P² + Q²

Power Factor: PF = P / S = cos(θ). Ranges from 0 to 1.0. PF = 1.0 means all power is real (purely resistive). Motors typically have PF 0.6–0.9.

Power Formulas

Circuit TypeReal Power (W)Apparent Power (VA)Current (A)
Single-phaseP = V × I × PFS = V × II = S / V
3-phase (line-to-line)P = VLL × I × PF × √3S = VLL × I × √3I = S / (VLL × √3)
3-phase (line-to-neutral)P = 3 × VLN × I × PFS = 3 × VLN × II = S / (3 × VLN)

Common Power Factors by Load Type

Load TypeTypical PFImpact on Sizing
Incandescent bulb1.0W = VA
LED driver0.9–0.95Minimal correction needed
Fluorescent (no PFC)0.5–0.6Needs capacitor correction
Induction motor (loaded)0.75–0.85Common in HVAC
Induction motor (light load)0.3–0.5Very poor PF
VFD (variable freq drive)0.95–0.98Good with input reactors
Welding transformer0.3–0.5Severe PF penalty

Why Power Factor Matters

Low power factor means higher current for the same real work. This increases:

Three-Phase Power

Three-phase power uses three alternating currents, 120° apart. It's more efficient for high-power loads:

Advantages:

SystemVoltageUse
208Y/120V 3-phase208V line-to-line, 120V line-to-neutralCommercial buildings
480Y/277V 3-phase480V line-to-line, 277V line-to-neutralCommercial/industrial
240V 3-phase delta240V (high-leg: 208V to neutral)Older commercial
600Y/347V 3-phase600V line-to-lineCanadian industrial

Common Mistakes

Standards Reference

Frequently Asked Questions

What's the difference between watts and VA?

Watts (W) is real power — the actual work done. VA (volt-amperes) is apparent power — total power delivered. For resistive loads (heaters, bulbs), W = VA. For reactive loads (motors), VA > W due to power factor. A motor with 960W and 0.8 PF has 1,200VA apparent power.

How do I calculate 3-phase power?

For 3-phase: P = V_LL × I × PF × √3. Example: 480V, 30A, PF 0.85: P = 480 × 30 × 0.85 × 1.732 = 21,195W ≈ 21.2 KW. The √3 factor accounts for the 120° phase relationship.

What is a good power factor?

A power factor above 0.90 is considered good. Most utilities require PF above 0.85 to avoid penalties. Motors are the most common cause of low PF — they typically run at 0.75–0.85. Power factor correction capacitors can improve PF to 0.95+.

Does low power factor increase my electric bill?

Yes, in two ways. First, your wiring carries more current for the same work, increasing I²R losses. Second, many commercial utilities charge a PF penalty when it drops below 0.85–0.90. Residential customers typically aren't penalized for PF.

How do I size a UPS for my equipment?

Add up the VA ratings (not watts) of all equipment, then add 20% margin. A computer drawing 300W at 0.6 PF has 500VA. For 3 computers: 1,500VA + 20% = 1,800VA UPS minimum. Check both the VA and watt ratings of the UPS — both must exceed your load.

Disclaimer: This guide is for educational and preliminary design purposes only. Always verify final equipment sizing against local codes and professional engineering requirements.