Power Factor Correction: Capacitor Sizing & Energy Savings

Quick Answer: To correct PF from 0.70 to 0.95: kVAR = kW × (tan(θold) − tan(θnew)). For a 100 kW load at PF 0.70: kVAR = 100 × (1.020 − 0.329) = 69.1 kVAR. Install a 75 kVAR capacitor bank. Annual savings: $2,000–$5,000 from avoided utility PF penalties.

Why Correct Power Factor?

Low power factor means high reactive current that does no useful work but still flows through your wiring, transformers, and utility lines. This causes:

Power Factor Triangle

PFcos(θ)tan(θ)Reactive/RealRating
1.001.0000.0000%Perfect
0.950.9500.32933%Excellent
0.900.9000.48448%Good
0.850.8500.62062%Acceptable
0.800.8000.75075%Below average
0.700.7001.020102%Poor
0.600.6001.333133%Very poor

Capacitor Sizing Formula

kVAR = kW × (tan(θold) − tan(θnew))

Or equivalently:

kVAR = kW × (√(1/PFold² − 1) − √(1/PFnew² − 1))

Quick Reference: kVAR per kW

From PFTo 0.90To 0.95To 0.98To 1.00
0.600.8491.0051.1081.333
0.650.6920.8480.9511.169
0.700.5360.6910.7941.020
0.750.3980.5530.6560.882
0.800.2660.4210.5240.750
0.850.1410.2960.3990.620
0.900.0000.1560.2580.484

Example: 100 kW load at PF 0.75, correct to 0.95: kVAR = 100 × 0.553 = 55.3 kVAR → install 60 kVAR bank.

Worked Example

Facility: 200 kW average demand, PF = 0.72, utility charges $1.50/kVAR for PF below 0.85.

Step 1: Current kVAR = 200 × √(1/0.72² − 1) = 200 × 0.964 = 192.8 kVAR

Step 2: Target kVAR at 0.95 PF = 200 × 0.329 = 65.8 kVAR

Step 3: kVAR to add = 192.8 − 65.8 = 127 kVAR

Step 4: Install 130 kVAR capacitor bank (next standard size)

Step 5: Penalty avoided: (192.8 − 65.8) × $1.50 = $190.50/month = $2,286/year

Step 6: Capacitor bank cost: ~$5,000–$8,000 installed

Step 7: Payback = $6,500 / $2,286 = 2.8 years

Common Power Factor Correction Mistakes

Standards Reference

Frequently Asked Questions

How do I calculate power factor correction?

Use kVAR = kW × (tan(θ_old) − tan(θ_new)). Find tan(θ) from your current PF: tan(θ) = √(1/PF² − 1). Example: 100 kW at PF 0.75 to 0.95: kVAR = 100 × (0.882 − 0.329) = 55.3 kVAR. Install a 60 kVAR capacitor bank.

What size capacitor for power factor correction?

Divide your kW load by the kVAR/kW factor from the table. For PF 0.75 → 0.95: multiply kW by 0.553. A 200 kW load needs 110.6 kVAR → install 120 kVAR. Always select the next standard size up and avoid over-correction above 0.98.

Is power factor correction worth it?

For commercial/industrial facilities with utility PF penalties: absolutely. Payback is typically 1–3 years. For residential customers: rarely worth it — most residential utilities don't charge PF penalties. The ROI depends on your utility rate structure and current PF.

Where do I install power factor capacitors?

Install at the main switchboard for facility-wide correction, or at individual motors for local correction. Main switchboard correction is simpler but doesn't reduce feeder losses. Motor-level correction reduces losses throughout the facility but costs more per kVAR.

Can capacitors cause harmonics?

Capacitors don't generate harmonics, but they can amplify existing harmonics by creating a resonance circuit with the system inductance. If total harmonic distortion (THD) is above 5%, use detuned reactors (typically 7% or 14% detuning) with the capacitors.

Disclaimer: This guide is for educational and preliminary design purposes only. Always verify final equipment sizing against local codes and professional engineering requirements.