Electrical Load Guide: NEC Article 220 Calculations

Quick Answer: Residential service sizing: 3 VA per sq ft (general lighting) + dedicated appliance loads at NEC demand factors. A 2,000 sq ft home with standard appliances typically needs 100–200A, 120/240V service. Use NEC 220.82 for optional residential method.

Why Load Calculations Matter

An electrical load calculation determines how much power a building needs. It sizes the service entrance, main breaker, panel, and feeders. An undersized service causes tripped breakers and voltage drop. An oversized service wastes money.

NEC 220.12 — General Lighting Load

OccupancyVA per sq ftNEC Reference
Dwelling unit3 VA/sq ft220.12
Office building3.5 VA/sq ft220.12
Restaurant2.0 VA/sq ftTable 220.12
Retail store3.0 VA/sq ftTable 220.12
Warehouse0.25 VA/sq ftTable 220.12
Hospital2.0 VA/sq ftTable 220.12
Hotel/Motel2.0 VA/sq ftTable 220.12

NEC 220.82 — Optional Residential Method

The simplified method for single-family dwellings:

  1. General loads: 3 VA/sq ft for lighting + 1,500 VA per small-appliance circuit (min 2 required) + 1,500 VA laundry circuit
  2. Appliance loads: Nameplate VA for dryer (5,000 VA min), range/oven, water heater, AC, etc.
  3. Demand factors:
    • First 10 kVA at 100%
    • Remaining at 40%

Worked Example: 2,000 sq ft Home

Step 1: General loads

Step 2: Appliance loads

Step 3: Apply demand factors (NEC 220.82(B))

Step 4: Service size

I = 19,800 / 240 = 82.5A → 100A service minimum (next standard breaker up)

Note: Most new homes install 200A service for future expansion (EV chargers, heat pumps, induction cooktops).

Common Dedicated Circuit Requirements (NEC 210)

CircuitRatingWireNEC Reference
Small appliance (kitchen)20A, 120V12 AWG210.11(C)(1)
Laundry20A, 120V12 AWG210.11(C)(2)
Bathroom20A, 120V12 AWG210.11(C)(3)
Refrigerator20A, 120V12 AWG210.52(B)(1)
Dishwasher20A, 120V (dedicated)12 AWG422.16
Dryer30A, 120/240V10 AWG210.52(C)
Range40-50A, 120/240V8-6 AWG210.52(C)

Common Load Calculation Mistakes

Standards Reference

Frequently Asked Questions

How do I calculate electrical load for a house?

Use NEC 220.82 optional method: 3 VA/sq ft for lighting + 1,500 VA per small-appliance circuit (min 2) + 1,500 VA laundry + all appliance nameplate VA. Apply demand factor: first 10 kVA at 100%, remainder at 40%. Divide total VA by 240V for service amps.

What size service do I need for a 2,000 sq ft house?

A typical 2,000 sq ft house with standard appliances needs approximately 80–100A calculated load. NEC allows rounding up to 100A service. However, most new homes install 200A service to accommodate future loads like EV chargers, heat pumps, and induction cooktops.

What are NEC demand factors?

Demand factors recognize that not all loads operate simultaneously. A building with 30 kVA of connected load doesn't need 30 kVA of service — NEC Table 220.42 and 220.82 provide standard reduction factors based on building type and load diversity.

Do I need a load calculation to add a subpanel?

Yes, if the existing panel is near capacity. Calculate the additional load, verify the existing service can handle it, then size the subpanel feeder accordingly. If the main breaker is already at 80% utilization, you may need a service upgrade.

How many circuits can I put in a 200A panel?

A 200A, 120/240V panel has 40,000VA capacity. The number of circuits depends on loads, not slots. A 40-slot panel can have 40+ circuits using tandem breakers. The limit is the total connected load vs the 200A main breaker, with NEC demand factors applied.

Disclaimer: This guide is for educational and preliminary design purposes only. Always verify final equipment sizing against local codes and professional engineering requirements.