Cooling Load Calculation: ASHRAE Heat Balance and RTS Guide

Quick Answer: For defensible commercial sizing, calculate envelope, solar, outdoor-air, occupant, lighting, and equipment gains by hour, separate sensible and latent loads, and find the coincident peak. ASHRAE's current nonresidential guidance centers on the Heat Balance (HB) and Radiant Time Series (RTS) methods; BTU/ft² is only a screening check.

What Is a Cooling Load?

The cooling load is the amount of heat energy that must be removed from a space per hour to maintain a desired indoor temperature. It's measured in BTU/h (or watts in metric). An accurate cooling load calculation ensures your AC system is properly sized — not too big, not too small.

The cooling load has multiple components:

Choose the Right Method: Heat Balance, RTS, or CLTD/CLF

The 2025 ASHRAE Handbook—Fundamentals, Chapter 18 presents two current nonresidential procedures: the rigorous Heat Balance (HB) method and the simplified Radiant Time Series (RTS) method. RTS retains an hourly workflow and accounts for the time delay between radiant heat gain and space cooling load.

MethodBest useWhat it capturesMain limitation
Heat BalanceDetailed simulation and final designSurface-by-surface convective and radiant balances at each hourInput- and computation-intensive
Radiant Time SeriesTransparent hourly commercial load calculationsSolar and nonsolar radiant gains converted to delayed hourly loadsStill requires schedules, weather, envelope, and zone inputs
CLTD/CLFLegacy calculations within the original table assumptionsApproximate time effects through tabulated factorsPrevious method; do not mix tables, climates, or constructions outside their applicability
BTU/ft² ruleEarly screening and reasonableness checksFloor area onlyCannot support final equipment selection

For a simple transparent check, steady window conduction can be written as Q = U × A × ΔT. Opaque-envelope and solar gains are time-dependent, so final peak sizing should use the selected hourly method instead of adding independent worst-case values from unrelated hours.

Infiltration and Ventilation Load

Qinf = 1.08 × CFM × (Tout − Tin)

Latent load (humidity): Qlat = 0.68 × CFM × (Wout − Win), where W is humidity ratio (gr/lb).

Internal Heat Gains

SourcePreliminary inputHourly calculation note
OccupantsPeople × activity-specific sensible and latent gainApply occupancy schedule and the method's radiant/convective split
LightingInstalled W × usage and allowance factorsConvert watts with 1 W = 3.412 BTU/h, then apply schedule and return-air treatment
Plug equipmentMeasured or nameplate W × load and diversity factorsDo not assume every device draws nameplate power at the same hour
Process or cookingProject-specific sensible and latent dataAccount for hoods, exhaust, makeup air, shielding, and operating schedule

Use these values only for preliminary screening. Final person, lighting, and equipment gains must come from the project's occupancy, schedules, nameplates, diversity assumptions, and applicable ASHRAE data.

Small-Commercial Cooling Load Workflow

  1. Define zones, construction assemblies, glazing orientation and shading, design weather, and indoor setpoints.
  2. Build hourly occupancy, lighting, plug-load, ventilation, and process schedules.
  3. Calculate envelope, fenestration, outdoor-air, and internal sensible and latent gains for every hour.
  4. Convert radiant gains to hourly space cooling loads with HB or RTS and identify each zone's coincident peak.
  5. Add system effects that are outside the zone model—such as fan heat, duct gains, or return-air paths—once, then select equipment against the documented design load and operating criteria.

Worked Subtotal: Internal Loads for a Small Office

At one occupied hour, assume 20 seated people at 450 BTU/h each, 20 desktop computers at 400 BTU/h each, and 2,000 W of lighting:

This is intentionally a subtotal, not the building cooling load. The final hourly calculation still needs envelope, solar, ventilation, infiltration, latent, and system effects. It also needs the sensible/radiant split and schedules used by the selected HB or RTS workflow.

Common Cooling Load Mistakes

Standards Reference

Frequently Asked Questions

How do you calculate cooling load for a room?

Build an hourly heat-gain model for envelope conduction, window solar gain, infiltration, ventilation, occupants, lighting, and equipment. Separate sensible and latent components, then use the ASHRAE heat balance or Radiant Time Series method to convert heat gains into the coincident peak cooling load.

What is the ASHRAE Radiant Time Series method?

The Radiant Time Series method is a simplified implementation of the heat balance method. It uses time-series factors to account for the delay between radiant heat gain and the resulting space cooling load, while retaining an hourly calculation workflow.

Can I size a commercial system using BTU per square foot?

Use BTU per square foot only as an early screening or reasonableness check. It does not capture orientation, glazing, schedules, ventilation, humidity, or coincident peaks, so final commercial equipment sizing needs an hourly load calculation.

What is the difference between sensible and latent cooling?

Sensible cooling lowers dry-bulb temperature. Latent cooling removes moisture. Calculate both because outdoor air, occupants, and process loads can add humidity even when their sensible contribution is modest.

What outdoor temperature should I use for cooling load calculation?

Use the applicable ASHRAE climatic design condition for the project location and system criteria. Do not substitute an all-time record temperature or stack an arbitrary safety factor onto every load component.

Is the CLTD/CLF method still valid?

CLTD/CLF is a legacy approximate method and should be used only within the assumptions and applicability of its original data. Current ASHRAE nonresidential guidance presents heat balance and Radiant Time Series as the principal methods.

Disclaimer: This guide is for educational and preliminary design purposes only. Always verify final equipment sizing against local codes and professional engineering requirements.