Phoenix, AZ outdoor design conditions

Phoenix, AZ Manual J outdoor design temperatures: 34°F winter 99% and 108°F summer 1%, with climate zone 2B.

ACCA Manual J Table 1Station screening referenceUpdated 2026-09-02

What this city design-condition page answers

Use the Phoenix, AZ values as outdoor starting points for a Manual J load calculation. Winter 34°F and summer 108°F are design percentiles, not an annual average and not a guarantee of equipment capacity at every hour. Climate zone 2B helps describe the envelope context but does not replace the selected weather station. The current screening station is Phoenix AP (USW00023183, 1113 ft). Phoenix is a hot-dry 2B climate where high summer dry-bulb and low outdoor moisture produce a different latent-load balance than Gulf Coast cities. Solar exposure and roof construction deserve explicit inputs.

This page is maintained by the HVAC Calculator Pro Editorial Team. We publish the inputs, calculation basis and limitations so a technician can reproduce the screening result and decide what must be checked in the field. It is a reference aid, not a substitute for the governing code, a licensed designer or the equipment manufacturer's instructions.

Winter 99%34 °F
Summer 1%108 °F
Climate zone2B

Manual J design inputs

Phoenix, AZ outdoor design conditions
FieldValueUse
Winter 99% dry bulb34 °Fheating design point
Summer 1% dry bulb108 °Fsensible cooling design point
IECC climate zone2Bconfirm governing station
Weather stationPhoenix APNOAA station reference
Station ID / elevationUSW00023183 / 1113 ftverify against current Manual J table
Wet bulb / daily rangeNot includedrequired when the load method calls for it

How to use this Phoenix, AZ design conditions

  1. Select the governing ACCA weather station for the project address.
  2. Enter winter and summer design values into a room-by-room Manual J load calculation.
  3. Add indoor setpoints, envelope, infiltration, orientation, internal gains and duct conditions; do not size from outdoor temperature alone.

Worked example: For Phoenix, use 34°F as the heating design point and 108°F as the cooling design point, then let the load calculation determine capacity.

Record the result with the project address, equipment model, code edition and assumptions. That audit trail is more useful than copying a single number without its conditions.

Continue with the right tool

What this city record does not include

Station selection, elevation, coincident wet-bulb, daily range, county microclimates and the building envelope can materially change the result. A city name is a convenient index, not a substitute for the project station.

For the governing reference, consult the current ACCA technical manuals and local code adoption.

Use boundary: This station record does not model county-level microclimates, elevation correction, coincident wet bulb or daily range. Use the governing station selected by a qualified designer.

Data sourceACCA Manual J Table 1 station values (https://www.acca.org/standards/technical-manuals); NOAA GHCN station metadata (https://www.ncei.noaa.gov/pub/data/ghcn/daily/ghcnd-stations.txt); verify the current edition and station selection.
Review statusScreening reference · not approved for final design
Last verified2026-09-02 · regenerate when the source or code edition changes

Common questions

Are these temperatures enough to size an HVAC system?

No. They are outdoor design inputs. Capacity requires a room-by-room load calculation with envelope, gains, infiltration and equipment data.

Why might a Phoenix project use a different station?

County, elevation and the project's governing code may point to another approved station. Confirm the station before final design.