R-22 pressure-temperature chart

R-22 pressure-temperature chart with bubble-point saturation pressure from -40°F to 140°F, generated from CoolProp.

Refrigerant R-22Bubble-point pressure37 rows

What this refrigerant PT chart answers

R-22 is a legacy HCFC refrigerant. Existing-system service must account for phase-out rules and refrigerant availability.

This page is maintained by the HVAC Calculator Pro Editorial Team. We publish the inputs, calculation basis and limitations so a technician can reproduce the screening result and decide what must be checked in the field. It is a reference aid, not a substitute for the governing code, a licensed designer or the equipment manufacturer's instructions.

Bubble-point saturation table

gauge pressure · sea-level reference
R-22 saturation pressure
TemperatureEquivalentPressure
-40 °F-40.0 °C0.6 PSIG
-35 °F-37.2 °C2.6 PSIG
-30 °F-34.4 °C4.9 PSIG
-25 °F-31.7 °C7.4 PSIG
-20 °F-28.9 °C10.2 PSIG
-15 °F-26.1 °C13.2 PSIG
-10 °F-23.3 °C16.5 PSIG
-5 °F-20.6 °C20.1 PSIG
0 °F-17.8 °C24.0 PSIG
5 °F-15.0 °C28.3 PSIG
10 °F-12.2 °C32.8 PSIG
15 °F-9.4 °C37.8 PSIG
20 °F-6.7 °C43.1 PSIG
25 °F-3.9 °C48.8 PSIG
30 °F-1.1 °C55.0 PSIG
35 °F1.7 °C61.5 PSIG
40 °F4.4 °C68.6 PSIG
45 °F7.2 °C76.1 PSIG
50 °F10.0 °C84.1 PSIG
55 °F12.8 °C92.6 PSIG
60 °F15.6 °C101.6 PSIG
65 °F18.3 °C111.2 PSIG
70 °F21.1 °C121.4 PSIG
75 °F23.9 °C132.2 PSIG
80 °F26.7 °C143.6 PSIG
85 °F29.4 °C155.7 PSIG
90 °F32.2 °C168.4 PSIG
95 °F35.0 °C181.8 PSIG
100 °F37.8 °C195.9 PSIG
105 °F40.6 °C210.8 PSIG
110 °F43.3 °C226.4 PSIG
115 °F46.1 °C242.8 PSIG
120 °F48.9 °C260.0 PSIG
125 °F51.7 °C278.0 PSIG
130 °F54.4 °C296.9 PSIG
135 °F57.2 °C316.7 PSIG
140 °F60.0 °C337.4 PSIG

How to use this R-22 pressure-temperature chart

  1. Identify the refrigerant and confirm the unit's design data plate.
  2. Measure line temperature at the same stable operating point as the gauge pressure.
  3. Use the chart to translate saturation temperature and then apply the manufacturer's superheat or subcooling procedure.

Worked example: At 40°F, use the table to estimate saturation pressure before comparing it with suction pressure and evaporator temperature. Use this chart to interpret a stabilized gauge reading on an existing R-22 system, then check leak, recovery and replacement requirements.

Record the result with the project address, equipment model, code edition and assumptions. That audit trail is more useful than copying a single number without its conditions.

Continue with the right tool

What is specific to R-22

Do not treat an R-22 table as permission to recharge a leaking system; local regulations and recovered-refrigerant rules still apply.

Safety and climate profile: Safety classification A1; approximate 100-year GWP 1,810; legacy HCFC subject to phase-out and service restrictions.

PSIG is gauge pressure. Absolute pressure adds local atmospheric pressure, so a gauge reading cannot be compared directly with an absolute-pressure chart without conversion.

For the governing safety and refrigerant-transition context, consult the U.S. EPA refrigerant guidance and the equipment manufacturer documentation.

Use boundary: This table does not model line pressure drop, superheat, subcooling, altitude correction or field safety controls. Confirm the correct blend basis and dew/bubble convention before using it.

Data sourceCoolProp 8.0.0 fluid properties (https://coolprop.org/); R-454B uses the published 68.9% R-32 / 31.1% R-1234yf mass blend converted to CoolProp molar fractions.
Review statusVerified dataset
Last verified2026-09-02 · regenerate when the source or code edition changes

Common questions

Can I use the R-22 pressure alone to charge a system?

No. Pressure must be interpreted with line temperature, airflow, operating mode and the manufacturer's charging method.

Why does this R-22 page say bubble point?

Bubble point is the saturated-liquid reference used by this generated table. Zeotropic blends may also require a dew-point reference, so the service procedure controls.