AWG to mm²: Complete Wire Gauge Conversion Guide

Quick Answer: AWG (American Wire Gauge) and mm² (metric) measure wire cross-sectional area. 14 AWG = 2.08 mm², 12 AWG = 3.31 mm², 10 AWG = 5.26 mm². Going down 3 AWG numbers doubles the area. Metric wire uses standard mm² sizes: 1.5, 2.5, 4, 6, 10, 16, 25 mm².

AWG vs Metric Wire Gauge

The American Wire Gauge (AWG) system is used in North America. The metric system (mm²) is used in Europe, Asia, and most of the world. They measure the same thing — wire cross-sectional area — but use different scales.

Key differences:

Complete AWG to mm² Conversion Chart

AWGDiameter (mm)Area (mm²)Area (cmils)Metric EquivalentCu Ampacity*
4/011.68107.2211,600120 mm²230A
3/010.4085.0167,80095 mm²200A
2/09.2767.4133,10070 mm²175A
1/08.2553.5105,60050 mm²150A
17.3542.483,69050 mm²130A
26.5433.666,37035 mm²115A
45.1921.241,74025 mm²85A
64.1113.326,25016 mm²65A
83.268.3716,51010 mm²50A
102.595.2610,3806 mm²35A
122.053.316,5304 mm²25A
141.632.084,1102.5 mm²20A
161.291.312,5801.5 mm²
181.020.8231,6201.0 mm²

*Ampacity at 75°C insulation (THWN). NEC 240.4(D) limits 14 AWG to 15A and 12 AWG to 20A for overcurrent protection.

Common International Wire Sizes

IEC mm²Nearest AWGAmpacity (Cu, 70°C)Common Use
0.520 AWG3ASignal, low-voltage
0.7518 AWG6ALighting, appliances
1.017 AWG10ALighting circuits
1.516 AWG13A10A lighting, 13A sockets (UK)
2.514 AWG18A16A power circuits (EU)
4.012 AWG24A20A power circuits
6.010 AWG31A32A circuits, cookers
108 AWG42ASubmains, motors
166 AWG56AFeeders, large motors
254 AWG73AService entrance

How to Convert AWG to mm²

Formula: A(mm²) = 0.01267 × 92^((36−AWG)/19.5)

Simplified for common gauges: each 3 AWG decrease ≈ 2× area.

14 AWG → 11 AWG ≈ 2× → 8 AWG ≈ 4× → 5 AWG ≈ 8× of 14 AWG area.

Common Mistakes

Standards Reference

Frequently Asked Questions

What is 12 AWG in mm²?

12 AWG = 3.31 mm² (nearest IEC size: 4 mm²). The actual cross-sectional area is 3.31 mm², which corresponds to a diameter of 2.05 mm. In IEC metric systems, 4 mm² wire is the standard equivalent.

What is 2.5 mm² in AWG?

2.5 mm² ≈ 14 AWG (actual: 2.08 mm²). The metric 2.5 mm² wire is slightly thinner than 14 AWG but is the standard IEC size used in European and Asian installations for 16A circuits.

Why does AWG decrease as wire gets bigger?

AWG is based on the number of drawing dies the wire passes through during manufacturing. More dies = thinner wire = higher gauge number. It's a historical manufacturing convention, not a measurement of size directly.

Can I mix AWG and metric wire?

Avoid mixing if possible. AWG and metric wires have slightly different diameters, which affects terminal connections. If you must splice them, use proper connectors rated for both sizes and verify the connection is tight.

What gauge wire do European countries use?

Europe uses IEC metric sizes: 1.5 mm² for lighting (10A), 2.5 mm² for power sockets (16A), 4 mm² for high-power circuits (20A), and 6 mm² for cookers and showers (32A). These are standardized across the EU under HD 60364.

Disclaimer: This guide is for educational and preliminary design purposes only. Always verify final equipment sizing against local codes and professional engineering requirements.