Wire Ampacity Guide: NEC 310.16 Complete Reference

Quick Answer: 14 AWG copper: 20A at 75°C insulation. 12 AWG: 25A. 10 AWG: 35A. NEC 240.4(D) limits 14 AWG to 15A and 12 AWG to 20A for overcurrent protection. Always derate for ambient temperature above 30°C and for 4+ conductors in a raceway.

What Is Ampacity?

Ampacity is the maximum current (amps) a conductor can carry continuously without exceeding its temperature rating. It depends on:

NEC Table 310.16 — Allowable Ampacities

AWG/kcmilCu 60°CCu 75°CCu 90°CAl 60°CAl 75°CAl 90°C
14152025
12202530152025
10303540253035
8405055304045
6556575405055
4708595556575
2951151307590100
1/0125150170100120135
2/0145175195115135150
3/0165200225130155175
4/0195230260150180205

Conditions: 30°C ambient, 3 or fewer current-carrying conductors, copper/aluminum conductors.

Temperature Derating (NEC Table 310.15(B)(2)(a))

When ambient temperature exceeds 30°C, multiply ampacity by the correction factor:

Ambient Temp60°C Insulation75°C Insulation90°C Insulation
30°C (base)1.001.001.00
35°C0.910.940.96
40°C0.820.880.91
45°C0.710.820.87
50°C0.580.750.82

Conductor Bundling Derating (NEC 310.15(B)(3)(a))

Current-Carrying ConductorsDerating Factor
1–31.00 (no derating)
4–60.80
7–90.70
10–200.50
21–300.45
31–400.40

Note: Neutral conductors in balanced 3-phase circuits don't count. In 120/240V single-phase, the neutral IS current-carrying (carries unbalanced load).

Worked Example: Derating

Scenario: 6 THWN copper conductors (12 AWG) in a conduit in an attic at 50°C.

Step 1: Base ampacity (75°C): 25A

Step 2: Ambient temp correction (50°C, 75°C insulation): × 0.75 → 18.75A

Step 3: Bundling correction (6 conductors): × 0.80 → 15A

Result: Each 12 AWG conductor can only carry 15A. Install on a 15A breaker (even though 12 AWG normally allows 20A).

Common Ampacity Mistakes

Standards Reference

Frequently Asked Questions

What is the ampacity of 12 AWG copper wire?

12 AWG copper wire has an ampacity of 25A at 75°C insulation (THWN) and 30A at 90°C (THHN). However, NEC 240.4(D) limits 12 AWG to 20A maximum overcurrent protection for residential branch circuits, regardless of the higher ampacity rating.

How does temperature affect wire ampacity?

Wire ampacity decreases as ambient temperature increases. At 40°C (104°F), 75°C-rated wire loses 12% of its ampacity. At 50°C (122°F), it loses 25%. In attics that reach 60–70°C, you may need to upsize wire significantly or use higher temperature-rated insulation.

What is the derating for 4 wires in a conduit?

NEC 310.15(B)(3)(a) requires 80% derating for 4–6 current-carrying conductors in a raceway. For example, 12 AWG rated 25A (75°C) becomes 20A with 4 conductors. This effectively limits 12 AWG to 20A (matching the NEC 240.4(D) limit).

Can I use the 90°C column for ampacity?

You can use the 90°C column for derating calculations (temperature and bundling), but the final ampacity must not exceed the 75°C column for termination at standard breaker and panel lugs. This is a two-step process: derate from 90°C, then compare to 75°C limits.

What's the difference between ampacity and overcurrent protection?

Ampacity is the wire's thermal capacity (how much current it can carry continuously). Overcurrent protection (breaker) is the maximum allowed by NEC. For 14 and 12 AWG, NEC 240.4(D) caps the breaker below the wire's ampacity for added safety.

Disclaimer: This guide is for educational and preliminary design purposes only. Always verify final equipment sizing against local codes and professional engineering requirements.