What Size Wire for 100 Amps? Breaker & Wire Chart

100 Amp Service Wire Chart

Wire MaterialSizeAmpacity (75°C)Conduit SizeCost/ft (approx)
Copper1/0 AWG125A1.5 inch$2.50–3.50
Aluminum2/0 AWG115A2 inch$1.00–1.80
Copper (continuous)1/0 AWG125A1.5 inch$2.50–3.50
Aluminum (continuous)3/0 AWG135A2 inch$1.50–2.20

Frequently Asked Questions

What size wire for 100 amps?

1/0 AWG copper (125A at 75°C) or 2/0 AWG aluminum (115A at 75°C) per NEC Table 310.16. For continuous loads: 100A × 1.25 = 125A → use 1/0 copper or 3/0 aluminum.

What size wire for a 100 amp sub panel?

1/0 AWG copper or 2/0 AWG aluminum for the feeder. Use 1.5 inch conduit for copper, 2 inch for aluminum. The sub-panel also needs a 4-wire feed: 2 hots + 1 neutral + 1 ground.

Can I run 100 amps on 2 AWG wire?

No. 2 AWG copper is rated for 95 amps (60°C) or 115 amps (75°C). At 75°C it technically works, but NEC 240.4(B) limits #2 copper to 100A maximum overcurrent protection. Use 1/0 AWG for a proper 100A installation.

Disclaimer: For preliminary design only. Verify against local codes and professional engineering requirements.