Motor Current Guide: FLC Tables & NEC 430 Requirements

Quick Answer: Motor wire must be sized for 125% of FLC (NEC 430.22). Breaker: 150% of FLC for inverse-time breaker (NEC 430.52). A 5 HP, 230V single-phase motor has FLC = 28A → wire: 8 AWG (35A), breaker: 40A.

Motor Nameplate vs FLC

Two current values matter for motors:

Why the difference? NEC tables use worst-case values for each HP rating. Your specific motor may be more efficient and draw less current. Always use NEC FLC tables for sizing — they provide a safety margin.

NEC Table 430.248 — Single-Phase FLC

HP115V200V230V
1/64.42.52.2
1/45.83.32.9
1/37.24.13.6
1/29.85.64.9
3/413.87.96.9
1169.28.0
1-1/22011.510
22413.812
33419.617
55632.228
7-1/2804640
1010057.550

NEC Table 430.250 — Three-Phase FLC

HP200V230V460V575V
1/22.52.21.10.9
14.23.61.81.4
27.86.83.42.7
3119.64.83.8
517.515.27.66.1
7-1/225.322119
1032.2281411
1548.3422117
2062.1542722
2578.2683427
3092804032
401201045241
501501306552

NEC 430 Motor Circuit Sizing Rules

ComponentSizing RuleNEC Reference
Wire (conductor)125% of motor FLC430.22
Overload protection115% of nameplate current (service factor 1.15: 125%)430.32
Branch circuit breaker (inverse-time)150% of FLC (250% for NEMA Design B motors)430.52
Branch circuit fuse (non-time-delay)300% of FLC430.52
Disconnect115% of motor FLC430.110
Ground wirePer NEC Table 250.122250.122

Worked Example

Motor: 10 HP, 230V, 3-phase, Design B.

FLC (Table 430.250): 28A

Wire: 28 × 1.25 = 35A → 8 AWG copper (50A at 75°C, but 40A at 60°C)

Breaker: 28 × 2.50 = 70A → 70A inverse-time breaker

Overload: 28 × 1.25 = 35A → set thermal overload relay to 35A

Disconnect: 28 × 1.15 = 32.2A → 40A disconnect

Ground wire: Table 250.122 for 70A breaker → 10 AWG copper

Common Motor Current Mistakes

Standards Reference

Frequently Asked Questions

How do I find motor full load current?

Use NEC Table 430.248 (single-phase) or 430.250 (three-phase) based on the motor's HP and voltage. Always use the table value, not the nameplate, for wire sizing and breaker selection. Nameplate current is for overload protection only.

What size wire for a 5 HP motor at 230V 3-phase?

NEC Table 430.250: FLC = 15.2A. Wire = 15.2 × 1.25 = 19A (NEC 430.22). Use 12 AWG copper (25A at 75°C). Breaker = 15.2 × 1.5 = 22.8A → 25A inverse-time breaker (NEC 430.52).

Why is motor breaker larger than wire ampacity?

Motor breakers (NEC 430.52) allow 150–250% of FLC to handle starting inrush current (6–8× FLC for 1–2 seconds). The overload relay protects the wire from sustained overcurrent. This is a specific exception to the standard NEC 240.4 wire-breaker matching rules.

Can I use a standard breaker for a motor?

Not recommended. Standard breakers (NEC 240.4) would trip on motor starting current. Motor circuit breakers (inverse-time) have a delay characteristic that allows the brief starting surge. Use motor-rated circuit breakers or time-delay fuses per NEC 430.52.

What happens if motor voltage is too low?

Low voltage causes the motor to draw higher current to maintain torque, leading to overheating and premature failure. At 10% below rated voltage, current increases ~10% and temperature rises ~15%. Keep voltage drop under 3% for motor circuits.

Disclaimer: This guide is for educational and preliminary design purposes only. Always verify final equipment sizing against local codes and professional engineering requirements.