← Back to calculators

Ampacity of Copper Wire by Gauge

Copper wire is the standard conductor material for most residential and commercial branch circuits due to its superior conductivity, reliability, and code compliance. This guide provides detailed ampacity tables for copper conductors broken down by wire gauge and insulation type—including THHN, THWN, THWN-2, XHHW, XHHW-2, and USE.

Why Insulation Type Matters for Ampacity

The ampacity of a conductor is not determined solely by its gauge (cross-sectional area). The insulation surrounding the conductor has a maximum operating temperature that directly limits how much current the wire can safely carry. Higher-temperature insulation allows the conductor to operate at higher ampacity because the wire can tolerate more heat before the insulation degrades.

NEC Table 310.16 organizes ampacity values by three temperature ratings: 60°C, 75°C, and 90°C. Each insulation type is assigned to one of these categories. Understanding which column applies to your wire—and to the termination points—is essential for proper conductor sizing.

Common Copper Wire Insulation Types

Insulation Type Temperature Rating Location Rating Description
TW60°C (140°F)Wet & DryThermoplastic, moisture-resistant. Older style insulation, largely replaced by THWN.
THW75°C (167°F)Wet & DryThermoplastic, heat and moisture resistant. Common in commercial wiring.
THHN90°C (194°F)Dry OnlyThermoplastic, high heat-resistant nylon jacket. Most common building wire for conduit and raceways.
THWN75°C (167°F)Wet & DryThermoplastic, heat and moisture resistant nylon jacket. Common in residential wiring.
THWN-290°C (194°F)Wet & DryUpgraded THWN with 90°C rating in both wet and dry locations. Dual-rated THHN/THWN-2 is widely available.
XHHW90°C (194°F)Dry OnlyCross-linked polyethylene (XLPE), high heat-resistant. Excellent abrasion and chemical resistance.
XHHW-290°C (194°F)Wet & DryUpgraded XHHW rated for wet locations. Popular for commercial and industrial applications.
USE / USE-275°C / 90°CUndergroundUnderground Service Entrance rated for direct burial. USE-2 has a 90°C rating.

Copper Wire Ampacity by Insulation Type

The following comprehensive table shows copper wire ampacities from 14 AWG through 4/0 AWG for each major insulation type. All values are based on an ambient temperature of 30°C (86°F) and no more than three current-carrying conductors in a raceway or cable.

Gauge 60°C Insulation 75°C Insulation 90°C Insulation
TW UF THW, THWN, USE THW-2 THHN, THWN-2, XHHW, XHHW-2, USE-2 Notes
14 AWG15A15A20A20A25AMax breaker: 15A (NEC 240.4D)
12 AWG20A20A25A25A30AMax breaker: 20A (NEC 240.4D)
10 AWG30A30A35A35A40AMax breaker: 30A (NEC 240.4D)
8 AWG40A40A50A50A55AMax breaker: 50A at 75°C
6 AWG55A55A65A65A75AMax breaker: 60A (next standard)
4 AWG70A70A85A85A95AMax breaker: 85A at 75°C
3 AWG85A85A100A100A110AMax breaker: 100A at 75°C
2 AWG95A95A115A115A130AMax breaker: 110A (next standard)
1 AWG110A110A130A130A150AMax breaker: 125A (next standard)
1/0 AWG125A125A150A150A170AMax breaker: 150A at 75°C
2/0 AWG145A145A175A175A195AMax breaker: 175A at 75°C
3/0 AWG165A165A200A200A225AMax breaker: 200A at 75°C
4/0 AWG195A195A230A230A260AMax breaker: 225A (next standard)

Note: For 14 AWG through 10 AWG, the usable ampacity at terminations is limited to the 60°C column per NEC 110.14(C)(1), regardless of insulation rating. For 8 AWG and larger, the 75°C column is typically usable when terminals are rated for 75°C.

Understanding Termination Temperature Limits

NEC 110.14(C)(1) is one of the most important and commonly misunderstood rules in electrical wiring. It states that the ampacity of a conductor must be based on the temperature rating of the termination or connection point—not just the wire insulation.

For circuits rated 100A or less (which covers 14 AWG through 1 AWG in most cases), the termination temperature limit is typically:

This means that even if you install THHN wire (rated 90°C), the usable ampacity at the breaker or panel termination is limited to the 75°C column value for 8 AWG and larger, or the 60°C column value for 14–10 AWG. The 90°C rating is only useful for derating calculations—it provides "headroom" when applying ambient temperature or bundling correction factors.

When Each Insulation Type Is Used

THHN/THWN-2 (Dual-Rated)

The most common wire type for residential and commercial conduit wiring. The dual-rated THHN/THWN-2 designation means it meets both the THHN standard (90°C, dry) and the THWN-2 standard (90°C, wet and dry). This versatile wire can be used in virtually any indoor or outdoor conduit application. It is available in sizes 14 AWG through 4/0 AWG and is the default wire pulled through EMT, PVC, and rigid conduit.

XHHW-2

XHHW-2 uses cross-linked polyethylene (XLPE) insulation instead of the PVC insulation used in THHN/THWN. XLPE offers superior abrasion resistance, chemical resistance, and slightly better performance at high temperatures. XHHW-2 is commonly used in commercial and industrial installations, particularly where conduit runs pass through areas with oils, solvents, or extreme temperatures. It is also commonly used in the conductors of MC (metal-clad) cable and some types of service entrance cable.

USE / USE-2

USE (Underground Service Entrance) cable is rated for direct burial without conduit. USE-2 is the upgraded version with a 90°C rating. USE cable is typically found in underground service entrance runs from the utility transformer to the meter base, and from the meter base to the main panel. Individual USE-2 conductors are also used in underground conduit runs where moisture is present.

TW and UF

TW (Thermoplastic, Water-resistant) is an older 60°C-rated insulation that has been largely replaced by THWN and THWN-2. UF (Underground Feeder) is a flat gray cable rated for direct burial, used for outdoor circuits to detached buildings, pumps, and landscape lighting. UF cable carries the same ampacity as TW at the 60°C rating.

How to Choose the Right Copper Wire

Follow this decision process to select the correct copper wire for your application:

  1. Calculate the circuit load in amperes. For continuous loads (3+ hours), multiply by 1.25 per NEC 210.19.
  2. Determine the installation environment. Indoor dry location? Outdoor wet location? Underground? This determines the required insulation type.
  3. Check termination ratings. Look at the breaker or equipment nameplate. Most residential breakers are rated 75°C. For 14–10 AWG, you are limited to the 60°C column regardless.
  4. Apply derating factors if applicable. Check ambient temperature corrections (NEC 310.15(B)(2)) and bundling corrections (NEC 310.15(B)(3)(a)). Use the 90°C column of the table as the base for derating calculations.
  5. Select the wire gauge. Choose a gauge whose ampacity at the applicable temperature column equals or exceeds the circuit load. Verify the breaker size does not exceed the ampacity per NEC 240.4.

Ampacity Comparison: Copper vs. Aluminum

Copper has approximately 61% higher conductivity than aluminum. This means that for the same gauge, copper wire carries significantly more current. To match the ampacity of copper, aluminum wire must be one to two sizes larger:

Application Copper Gauge (75°C) Aluminum Gauge (75°C) Ampacity
15A circuit14 AWG12 AWG15–20A
20A circuit12 AWG10 AWG20–25A
30A circuit10 AWG8 AWG30–40A
50A circuit6 AWG4 AWG50–65A
100A service2 AWG1/0 AWG100–120A
200A service3/0 AWG4/0 AWG200–230A

For a complete comparison, see our Wire Ampacity Chart.

When to Use a Calculator

Selecting copper wire involves balancing ampacity, insulation type, termination ratings, derating factors, and voltage drop. Our Wire Size Calculator handles all of these variables automatically. Enter your circuit load, distance, ambient temperature, and conductor count to get an NEC-compliant wire recommendation instantly.

Frequently Asked Questions

What is the ampacity of 10 AWG copper wire?

10 AWG copper wire has an ampacity of 30A at 60°C, 35A at 75°C, and 40A at 90°C per NEC Table 310.16. However, for branch circuit terminations rated at 60°C or 75°C, the usable ampacity is 30A or 35A respectively.

What is the difference between THHN and THWN wire?

THHN is rated for 90°C in dry locations only, while THWN is rated for 75°C in both wet and dry locations. THWN-2 is rated for 90°C in wet and dry locations. THHN has a nylon jacket over PVC insulation; THWN has a moisture-resistant PVC jacket.

Can I use THHN wire in wet locations?

No. Standard THHN wire is rated for dry locations only. For wet locations, use THWN, THWN-2, or XHHW-2. Dual-rated THHN/THWN-2 wire is common and can be used in both wet and dry locations.

What insulation type should I use for underground wire?

For underground or direct burial applications, use USE (Underground Service Entrance) or USE-2 rated wire. UF (Underground Feeder) cable is also rated for direct burial. XHHW-2 may be used in conduit underground.

Does insulation type affect the breaker I can use?

For 14-10 AWG conductors, NEC 110.14(C)(1) limits the termination temperature to 60°C regardless of insulation type, so the breaker selection is based on the 60°C ampacity column. For 8 AWG and larger, 75°C ratings are typically usable with modern breakers.

Try the Wire Size Calculator →