CFM Calculator: Airflow Requirements for Every Room

Quick Answer: The standard residential ventilation rate is 1 CFM per 1 sq ft of floor area (ASHRAE 62.2), or 0.35 ACH (air changes per hour), whichever is larger. A 200 sq ft bedroom needs about 75 CFM minimum ventilation.

What Is CFM?

CFM (Cubic Feet per Minute) measures the volume of air flowing through a space per minute. In HVAC, CFM determines how much conditioned air reaches each room, directly affecting comfort, air quality, and energy efficiency.

Key relationships:

CFM Requirements by Room Type

Room TypeCFM/sq ftMin CFM (small room)Standard
Living Room1.0100 CFMASHRAE 62.2
Bedroom0.5–1.075 CFMASHRAE 62.2
Kitchen (range hood)N/A100 CFM intermittentASHRAE 62.2
Bathroom (exhaust)N/A50 CFM continuous / 80 CFM intermittentASHRAE 62.2
Laundry RoomN/A100 CFMIRC M1505
Garage1.0 (if conditioned)100 CFMIMC 403
Office0.5–1.050 CFM/personASHRAE 62.1

CFM Per Ton of AC

The standard airflow for cooling systems is 400 CFM per ton (12,000 BTU/h). This is the nominal airflow across the evaporator coil.

AC SizeBTU/hStandard CFMAcceptable Range
1 ton12,000400350–450
1.5 ton18,000600525–675
2 ton24,000800700–900
2.5 ton30,0001,000875–1,125
3 ton36,0001,2001,050–1,350
4 ton48,0001,6001,400–1,800
5 ton60,0002,0001,750–2,250

Note: In humid climates, use 350 CFM/ton for better dehumidification. In dry climates, up to 450 CFM/ton is acceptable.

How to Calculate CFM

Method 1: Area-Based (Simple)

CFM = Area (sq ft) × CFM/sq ft

Example: 250 sq ft living room × 1.0 CFM/sq ft = 250 CFM

Method 2: Air Changes Per Hour (ACH)

CFM = (Room Volume × ACH) ÷ 60

Example: 250 sq ft × 8 ft ceiling = 2,000 cu ft. Target 6 ACH.

CFM = (2,000 × 6) ÷ 60 = 200 CFM

Method 3: Duct Velocity

CFM = Velocity (FPM) × Duct Area (sq ft)

Example: 600 FPM through a 10" × 8" duct (0.56 sq ft).

CFM = 600 × 0.56 = 336 CFM

CFM Chart by Duct Size

Duct Size (inches)Area (sq in)CFM @ 500 FPMCFM @ 700 FPMCFM @ 900 FPM
6" round28.398138177
8" round50.3175245314
10" round78.5273382490
12" round113.1393550706
4×10 rectangular40139194250
6×10 rectangular60208292375
8×12 rectangular96333467600

Common CFM Mistakes

Standards Reference

Frequently Asked Questions

How many CFM do I need per room?

ASHRAE 62.2 requires 1 CFM per sq ft for living areas, 0.35 ACH whole-house ventilation (whichever is greater), 50 CFM continuous for bathrooms, and 100 CFM intermittent for kitchens. A 200 sq ft bedroom needs about 75–200 CFM depending on occupancy and ventilation strategy.

How many CFM per ton of AC?

The standard is 400 CFM per ton of cooling capacity. This is the airflow across the evaporator coil. In humid climates, reduce to 350 CFM/ton for better moisture removal. In dry climates, 450 CFM/ton is acceptable. Going below 300 CFM/ton risks coil freezing.

What CFM bathroom fan do I need?

ASHRAE 62.2 requires 50 CFM continuous or 80 CFM intermittent for bathrooms up to 100 sq ft. For larger bathrooms, use 1 CFM per sq ft. Always vent to the exterior, never into the attic.

How does duct size affect CFM?

Duct size directly determines CFM capacity at a given velocity. A 6" round duct handles ~100 CFM at 500 FPM. An 8" round handles ~175 CFM. Undersized ducts create high static pressure, noise, and reduced airflow. Use ACCA Manual D for proper duct sizing.

Can I have too much CFM?

Yes. Excessive CFM causes drafts (air velocity >50 FPM at the register is uncomfortable), noise, and energy waste. For supply registers, keep throw velocity under 750 FPM in living areas and 500 FPM in bedrooms.

Disclaimer: This guide is for educational and preliminary design purposes only. Always verify final equipment sizing against local codes and professional engineering requirements.