Insulation Resistance Calculator

Temperature-corrected IR test with pass/fail analysis

Input Parameters

About This Calculator

  • R_ref = R_meas × 2^((T_meas - T_ref)/10)
  • Min IR = kV rating + 1 MΩ (IEEE 43)
  • Insulation resistance halves per 10°C rise

📖 Read the Complete Guide →

How this insulation resistance calculator works

Insulation resistance decreases with temperature. The correction formula: R_ref = R_measured × 2^((T_measured - T_ref)/10).

The IEEE 43 standard minimum: equipment voltage (kV) + 1 MΩ. For a 480V motor, minimum = 1.48 MΩ.

FAQ

What is IR testing?

Megger test measures insulation quality with high DC voltage.

Temperature correction?

R doubles for every 10°C drop. Corrected to 20°C reference.

kV+1 rule?

Min IR = kV rating + 1. 480V equipment needs ≥1.48 MΩ.