Branch Takeoffs duct sizing chart

Branch duct sizing chart by airflow at 0.10 inch water-column friction rate, with a transparent screening method.

ACCA Manual DScreening reference0.10 in. w.c. / 100 ft

What this duct sizing chart answers

Branch takeoffs should be sized from room airflow, not from equipment tonnage alone.

This page is maintained by the HVAC Calculator Pro Editorial Team. We publish the inputs, calculation basis and limitations so a technician can reproduce the screening result and decide what must be checked in the field. It is a reference aid, not a substitute for the governing code, a licensed designer or the equipment manufacturer's instructions.

Airflow to duct size

screening reference
branch takeoffs duct sizing at 0.10 in. w.c. per 100 ft
Airflow CFMSuggested sizeVelocity fpmEstimated friction in. w.c. / 100 ft
1006 in5090.086
1507 in5610.085
2008 in5730.074
2509 in5660.063
3009 in6790.088
40011 in6060.055
50012 in6370.055
60013 in6510.051
80015 in6520.043
100017 in6340.035
120018 in6790.037
160021 in6650.030
200023 in6930.029

Field interpretation

The smaller target velocity used here is a screening aid for branch noise; balancing dampers and terminal pressure still need to be selected.

Definitions: Airflow is the design volume in CFM; cross-sectional area links CFM to velocity; velocity is the average air speed in fpm; friction rate is the pressure-loss target per 100 ft; equivalent length converts fittings and transitions into comparable straight-run loss.

Worked example: For a 150 CFM bedroom branch, use the row as a candidate and then check the grille throw and available static pressure.

The generated row uses area and target velocity to create a candidate and reports a Darcy-Weisbach friction estimate for round ducts. Rectangular and flex corrections, fittings and the blower pressure budget still require a Manual D worksheet.

How to use this branch takeoffs sizing chart

  1. Start with the room or trunk airflow from a load calculation.
  2. Choose a candidate size and record the assumed friction target and velocity.
  3. Add straight-run length, equivalent fitting length, filter, grille and terminal losses before approving the design.

Worked example: A chart row is a candidate dimension, not a guarantee that the installed system will deliver its design airflow.

Record the result with the project address, equipment model, code edition and assumptions. That audit trail is more useful than copying a single number without its conditions.

Continue with the right tool

Use boundary: This chart does not include fitting equivalent lengths, duct heat gain/loss, acoustic limits, altitude correction or a room-by-room Manual J airflow. Verify the longest run with a ductulator or Manual D worksheet.

Data sourceASHRAE duct design references (https://www.ashrae.org/technical-resources/standards-and-guidelines) and ACCA Manual D conventions (https://www.acca.org/standards/technical-manuals); this page uses a transparent target-velocity screening calculation plus a Darcy-Weisbach estimate.
Review statusScreening reference · not approved for final design
Last verified2026-09-02 · regenerate when the source or code edition changes

Common questions

Is this a final Manual D duct size?

No. It is a screening candidate based on airflow, area and target velocity. Final sizing must include friction, fittings, terminals and the blower pressure budget.

Why can two ducts with the same CFM need different sizes?

Shape, roughness, flex compression, fitting losses and the available static pressure change the acceptable size.